![Azbil Micro Flow MQV0005 Скачать руководство пользователя страница 57](http://html1.mh-extra.com/html/azbil/micro-flow-mqv0005/micro-flow-mqv0005_user-manual_3042629057.webp)
5-11
Chapter 5. ADVANCED OPERATION
*8 If “5,” “6,” or “8” (operation mode switching) is selected for one of the external contact input func-
tion assignments (
C-
10
to
C-
12
) and if the valve is set to fully closed or fully open mode by
external contacts, the operation mode cannot be switched using the [RUN] key.
If the valve is set to control mode by external contacts, the operation mode can be switched
using the [RUN] key.
Based on the settings for
C-
10
to
C-
12
, the operation mode changes in accordance with the
input status as shown in the table below.
C-
10
to
C-
12
settings
Status of external contact input
ON
OFF
5
Fully closed mode
Control mode
Operation mode can be switched between control
/ fully closed / fully open using the [RUN] key.
6
Fully open mode
Control mode
Operation mode can be switched between control
/ fully closed / fully open using the [RUN] key.
8
Control mode
Operation mode can be switched be-
tween control / fully closed / fully open
using the [RUN] key.
Fully open mode
Handling Precautions
•
When the operational differential pressure setting (
C-36
) is changed
to "0: Low differential pressure (50 ± 50 kPa)," always use the device
with an operational differential pressure less than 100 kPa. Failure to
do so may cause overshoot or hunting of the flow rate.
Содержание Micro Flow MQV0005
Страница 34: ......
Страница 46: ......
Страница 66: ......
Страница 71: ...7 1 Chapter 7 SPECIFICATIONS Individual specifications Please go to the next page...
Страница 88: ......
Страница 90: ...Specifications are subject to change without notice 10 1st edition Dec 2006 U 4th edition June 2019 V...