Chapter 4. BASIC OPERATION
Digital flow rate setup
Up to eight SP values can be set on this device. The operating proce-
dure may vary depending on the number of SP values to be set.
z
Single setup (number of SPs in function setup
C-04
is 1)
Follow the procedure below to change the SP value:
(1) Press the
[DISP]
key.
>> The SP (flow rate setpoint) is shown on the 7-segment display
(2) Change the SP value by pressing the
[
▲
]
key or
[
▼
]
keys. You
can move to the digit to be changed by pressing the
[
]
key.
>> The digit currently being changed starts blinking.
(3) When you have reached the target value, press the
[ENT]
key.
>> The SP value is set, and saved.
Note (Advanced use, direct setup function)
•
Control can be executed using an SP value currently being
changed (indicated by blinking display) when the direct setup
function is enabled for the instantaneous flow rate direct setup
function ON/OFF (
C-2
1
in the function setup). In this case, the
[ENT]
key need not be pressed to enter the SP value.
Handling Precautions
•
When switching the display by pressing the [DISP] key, first
press the [ENT] key to enter the SP value, and switch the dis-
play.
For details on how to set up functions,
z
Multi-setup (number of SPs in function setup
C-04
is 2 to 8)
In multi-setup, up to eight SP values can be switched by key operation
and by external contact input.
Follow the procedure below to change the SP No. and SP value:
(1) Press the
[DISP]
key.
>> The display switches to SP No.
SP-0
to
SP-7
after about one
second.
(2) Press the
[
▲
]
or
[
▼
]
keys to change the SP No. and press the
[ENT]
key.
>> The SP No. is entered.
(3) Change the SP value by pressing the
[
▲
]
or
[
▼
]
keys. You can
move to the digit to be changed by pressing the
[
]
key.
>> The digit currently being changed blinks while the SP value is
being changed.
(4) When you have reached the target value, press the
[ENT]
key to
enter the new SP value.
>> The SP value and SP No. are updated, and the SP value of the
selected SP No. is new the active SP.