5-14
Chapter 5. ADVANCED OPERATION
No.
Display
Description
Factory Setting
Setting Range
Related
Function
Setup
Remarks
19
E.a.HI
*
11
Totalized flow event
setting (first 4 digits)
0
0 to 9999
20
P.0.Dl
*
12
PV forced zero func-
tion delay
3.0 s
0.0 to 999.9 s
C-29
21
SP.l.H
*
13
SP upper limit flow rate
100 % FS
(1.00) *
14
0 to 100 % FS
(0.0 to 1.00) *
14
C-35
Unit: L/min (standard)
22
SP.l.L
*
13
SP lower limit flow rate
0 % FS
(0.0) *
14
0 to 100 % FS
(0.0 to 1.00) *
14
*1. Operation during judgment of flow rate OK.
SP
PV
ON (OK)
OFF
0
.
hy5
0
.
hy5
0
.
r
G
0
.
r
G
*2. Operation during judgment of flow rate deviation upper and lower limit alarms
Be sure to set so that
a.lO
≥
a.L.hy
or
a.hi
≥
a.h.hy.
SP
PV
ON (ALM)
OFF
a
.
h
.
hy
a
.
L
.
hy
a
.
hi
a
.
lO
*3. Only items corresponding to the alarm type selected in flow rate alarm setup (
c-
15
in the func-
tion setup) can be set.
*4. These alarms can be set when (1 to 3) is set for flow rate alarm setup type (
c-
15
) and valve am-
perage alarm setup type (
c-
20
) in the function setup.
*5. T his cannot be set when "0: Not used (OFF all times)" has been selected for
c-
07
and
c-
08
event output type assignment in the function setup.
*6. This can be set only when "0: Conversion factor for each gas type set by the user" has been se-
lected for the
c-
18
or
c-
26
gas type selection 1 or 2 in the function setup.
*7. This can be set only if a suitable alarm type is selected in the
c-
20
valve amperage alarm setup
(in the function setup).
*8. This can be set only when "8 to 10: PV upper / lower limit event 1, 2" has been selected for the
c-
07
and
c-
08
event output type assignment in the function setup.
*9. This can be set only when "1 and 2: SP ramp control" has been selected for the
c-
27
SP ramp
control function in the function setup.
*10. This can be set only when "1: Function enabled" has been selected for the
c-
28
analog op-
tional scaling function in the function setup.