Electrical wiring
Azbil Corporation
3-4
Model MCB10A
Wire connection for pulse output
The pulse output is an open-collector output.
Do wiring work paying attention to the voltage and polarity.
Load
Protective diode
+
-
-
+
PULSE OUT +
PULSE OUT -
External power source
30V DC max.
100mA max.
Avoid this polarity
Figure 3-2 Pulse output wire connection diagram
Wire connection for contact output
Because of the open-collector output, do wiring work paying attention to the voltage
and polarity.
Load
Protective diode
+
-
-
+
STATUS OUT +
STATUS OUT -
External power source
30V DC max.
100mA max.
Avoid this polarity
Figure 3-3 Contact output wire connection diagram