Operation using the data setting device
Azbil Corporation
5-26
Model MCB10A
5-6-2 : Selecting pulse output or contact output
Pulse output or contact output are selectable. Both of them are open collector outputs.
When pulse output has been selected:
Set pulse scale, pulse width, drop out, and burn out.
When contact output has been selected:
As a contact output, self diagnosis output (critical failure) or upper/lower
limit alarm is output.
Select % flow rate value for upper/lower alarm or output status (OPEN or
CLOSE in normal (normal state)).
Setting range: PULSE: Selection of pulse output
STOUT: Selection of contact output
Default:
PULSE
Select pulse output or contact output in accordance with the following procedure:
Step
Procedure
Screen
1
Enter ENGINEERING MODE in accordance
with the entry into ENGINEERING MODE
(see section 5-4-10). Then press the
h
or
i
key to display the screen at right.
20.0 %
# FUNCSET
PULSE
2
Press the
g
key to move the cursor to the
position for set function.
Press the
h
or
i
key to display a function to
be set. Select either PULSE (pulse output) or
STOUT (contact output).
20.0 %
# FUNCSET
PULSE
20.0 %
# FUNCSET
STOUT
3
Press the MODE key to return to the
MEASURING MODE and to save data.
20.0 %
# FUNCSET
STOUT
CAUTION
You have only ten minutes to return to MEASURING MODE to save the new
value before the system resets it to the previously saved value.