DSP resolver user manual
User Manual
Version 1.15
index
h
su
b
obj.
variable
type
b
yt
es
acce
ss
M/
O
pd
o
profile value
Default
value
value range
notes
1800
0
RECORD co_tpdo_comm_par[0]
RO
C/m
n
2 - 5
5
5
Communication parameters for the first transmit PDO
1
U32
4
RW
m
n
0x180 +
nodeID
0x4000
0000
PDO COB-ID
If CAN-ID is zero, sw will calculate default CAN-ID
Bits 0 – 10
11 bit CAN-ID
Bits 11 – 28
Extension of the 29 bit CAN ID, always 0
Bit 29
Frame bit, only 11-bit Ids supported -> always 0,
Bit 30
RTR, always 1 , RTR messages not supported
Bit 31
Valid bit, 1 -> pdo disabled, 0 -> pdo enabled
2
U8
1
RW
m
n
0xFF
0xFE
0x01 ... 0xF0,
0xFE , 0xFF
Transmission type.
0: Acyclic, synchronous
1 – 240 (0x1- 0xF0): Cyclic, synchronous
252: Synchronous, RTR only. Not supported
253: Asynchronous, RTR only. Not supported
254: Asynchronous
255: Asynchronous
Synchronous transmission means that the transmission is related to SYNC
object. PDO will be transmitted after SYNC receiving the SYNC message.
Asynchronous transmission means that the transmission in non related to
SYNC object. Transmission type zero means that message will be
transmitted synchronous but not periodically. Transmission type 1 – 240
in cyclic transmission indicates how many SYNC messages is needed trig
PDO to transmitted. 254 means that asynchronous transmission is
manufacturer specific and 255 means that the transmission is device
profile specific.
3
U16
2
RW
o
n
0 (DS406 )
0
Inhibit time.
The minimum interval for PDO transmission. Multiply of 100
microseconds. Not supported
4
U8
1
RW
o
n
0
Reserved
5
U16
2
RW
o
n
0 (DS406)
50
0....0xfffffff
Event timer.
0: Not used
In asynchronous transmission mode event timer defines transmission
interval. The value is a multiply of one millisecond.