DSP resolver user manual
User Manual
Version 1.15
Error
code
Meaning
Support note
Error bit in error
register (index 1001)
0x0000
Error reset or no error
0x1000
Generic error
Generic
0x4200
Processor temperature
too high
not supported
0x6250
Incompatible hw and
sw
GManufacturer
specific
0x6350
automatic object
dictionary restoring
occured
Software has automatically restored
the object dictionary
GManufacturer
specific
0x8110
CAN overrun (Objects
lost)
not supported
0x8120
CAN in error passive
mode
not supported
0x8130
Heartbeat error
not supported
0x8140
Recovered from bus off
not supported
0x8210
PDO not processed due
to length error
not supported
0x8220
PDO length exceeded
not supported
0xFF10
Sensor failure detected
GManufacturer
specific
Table 7.10: Supported emergency (EMCY) message error codes
Error bits resulting from the EMCY messages are listed in table below.
bit
Error type
Support note
0
Generic
Set if generic or any other error is present
1
Current
not supported
2
voltage
not supported
3
temperature
not supported
4
communication
not supported
5
Device profile specific
not supported
6
reserved
Always 0
7
Manufacturer specific
Set if error is valid
Table 7.11: Error bits in error register (index 1001)
7.2.4
CAN bus baudrate
Every device connected to the CAN bus has to use same baudrate. Baudrate can be changed
with the LSS protocol ( a CAN open sub protocol) or trough RS232 interface with a
#SBxx!
command. The LSS protocol is described in details in CANopen manual chapter.
The serial protocol command is
#SBxx!
where xx is serial command index. Supported
baudrate values and correlated indexes for LSS and serial commands are listed in table xx.
Baudrate of an unconfigurated device is 125 kbit/s.