User Manual UMAX030541. Version V1 69-116
3.3.14 Object 7341h: AO Fault Field Value
This object contains the pre-defined field value of an analog output when a fault condition
is present, and the corresponding sub-index in object 7341h is enabled. It will be scaled
in the physical unit of the output, dependent on type, with the resolution defined in object
6332h AO Decimal Digits FV.
Object Description
Index
7341h
Name
AO Fault Field Value
Object Type
ARRAY
Data Type
INTEGER16
Entry Description
Sub-Index
0h
Description
Largest sub-index supported
Access
RO
PDO Mapping
No
Value Range
4
Default Value
4
Sub-Index
1h to 4h (x = 1 to 4)
Description
AOx Fault Field Value
Access
RW
PDO Mapping
No
Value Range
Dependent on range (see Table 4)
Default Value
0 [mV]