User Manual UMAX030541. Version V1 80-116
3.4.12 Object 2352h: AO Enable Response
This object determines if the input will act as an enable or safety interlock (i.e. input must
be ON to engage the output) or a disable signal (i.e. the output will shutoff when the input
is ON.) The options for this object for analog output 1 to 2 are listed in Table 9.
Object Description
Index
2352h
Name
AO Enable Response
Object Type
ARRAY
Data Type
UNSIGNED8
Entry Description
Sub-Index
0h
Description
Largest sub-index supported
Access
RO
PDO Mapping
No
Value Range
4
Default Value
4
Sub-Index
1h to 4h (x = 1 to 4)
Description
AOx Enable Response
Access
RW
PDO Mapping
No
Value Range
See Table 9
Default Value
3 (Enable When Off, Else Shut Off )
3.4.13 Object 2360h: AO Override Input Source
This object defines the type of input that will be used to active the override value for the
analog outputs as shown in the logic flowchart in Figure 5. The available control sources
on the CAN-4AOUT controller are listed in Table 5. Not all sources would make sense to
enable the AO, and it is the user’s responsibility to select a source that makes sense for
the application.
Object Description
Index
2360h
Name
AO Override Input Source
Object Type
ARRAY
Data Type
UNSIGNED8