User Manual UMAX030541. Version V1 49-116
By read access, the object provides information about the module’s default parameter
restoring capabilities. For all sub-indexes, this value is 1h, indicating that the controller
restores defaults on command.
Object Description
Index
1011h
Name
Restore Default Parameters
Object Type
ARRAY
Data Type
UNSIGNED32
Entry Description
Sub-Index
0h
Description
Largest sub-index supported
Access
RO
PDO Mapping
No
Value Range
4
Default Value
4
Sub-Index
1h
Description
Restore all default parameters
Access
RW
PDO Mapping
No
Value Range
0x64616F6C (write access), 1h (read access)
Default Value
1h
Sub-Index
2h
Description
Restore default communication parameters
Access
RW
PDO Mapping
No
Value Range
0x64616F6C (write access), 1h (read access)
Default Value
1h
Sub-Index
3h
Description
Restore default application parameters
Access
RW
PDO Mapping
No
Value Range
0x64616F6C (write access), 1h (read access)
Default Value
1h
Sub-Index
4h
Description
Restore default manufacturer parameters
Access
RW
PDO Mapping
No
Value Range
0x64616F6C (write access), 1h (read access)
Default Value
1h