3.4.68 Object 5033h: Hysteresis to Clear Temperature Fault
This object is used to set the value by which the temperature needs to decrease to clear
the fault set by an over temperature event. If object 5031h is disabled, this value is
ignored. For more information, please refer to Section 1.7.
Object Description
Index
5033h
Name
Hysteresis to Clear Temperature Fault
Object Type
VARIABLE
Data Type
UNSIGNED8
Entry Description
Sub-Index
0h
Access
RW
PDO Mapping
No
Value Range
0…150 (DegC)
Default Value
25 (DegC)
3.4.69 Object 5034h: Enable Temperature Fault Shutdown
This write-able object is available to enable shutdown when there are faults on
temperature measured in the system. For more information, please refer to Section 1.7.
Object Description
Index
5034h
Name
Enable Temperature Fault Shutdown
Object Type
VARIABLE
Data Type
UNSIGNED8
Entry Description
Sub-Index
0h
Access
RW
PDO Mapping
No
Value Range
FALSE; TRUE
Default Value
TRUE (1)
3.4.70 Object 5550h: Enable Automatic Updates
This object allows the controller to update objects to defaults automatically when an
output type is changed. Be default this object is TRUE.