Installing the Avaya S8700 Media Server with an Avaya G650 Media Gateway
69
December 2003
Figure 3, Front view of an G650 Media Gateway,
on page 69 shows the placement of circuit packs in the
G650 Media Gateway.
Figure 3: Front view of an G650 Media Gateway
Checking the ventilation and the G650 Media
Gateway rack
!
WARNING:
Make sure there is adequate ventilation in the area. The internal room temperature must not exceed
104
o
F (40
o
C).
For adequate ventilation and to conform with EIA-310D data rack standards, you need to provide the
following clearance:
•
12 inches (30 centimeters) in the rear
•
18 inches (45 centimeters) in the front
•
3 inches (7.6 centimeters) on the sides
!
WARNING:
Be sure the customer-supplied 19-inch (48-centimeter), EIA-310D standard, open rack is properly
installed, solidly secured to the floor, and grounded. If the rack is not secured to the floor, do not
proceed with the installation. Avaya does not recommended that you use enclosed data cabinets,
because they might not allow sufficient ventilation to the G650 Media Gateway.
Figure notes
1
ESD ground jack
2
655A power supply
3
TN2312BP IP server interface circuit
pack (in carrier A or B only)
4
TN799DP C-LAN
5
TN2302 IP Media Processor
FAN OR POWER FAIL
FAN AND POWER OK
AC INPUT
DC INPUT
ACTIVE RING
FAN OR POWER FAIL
FAN AND POWER OK
AC INPUT
DC INPUT
ACTIVE RING
10
3
4
5
6
8
9
Power
2
7
11
12
13
Power
1
14
2
1
5
3
4
scdlff02 LAO 081203
2