In the Event of a Fire Alarm
Operator's Handbook, AutroSafe Interactive Fire Alarm System, Release 3, ASAFE-FO/FE Rev. E, 021105,
Autronica Fire and Security AS
Page 34
Step
Actions to be taken
Display Indication
Audible Indication
9
To silence all alarms,
press the red Silence
Alarms button.
All Fire Alarm Devices
(FAD) are deactivated.
Comments:
The red
FIRE
indicator goes steady.
To
manually
resound the alarm zones at this stage, Action Digit 1
(RESOUND) can be pressed.
The alarm zones are
automatically
resounded to their alarm states on
timeout of the silence resound timer.
When the fire is extinguished and all necessary repair work is implemented
(smoke is exhausted, new glass replaced in the manual call-points, etc.), the
system should be returned to normal operating mode.
The SILENCE ALARMS button has to be pressed before pressing the
RESET button. Otherwise the reset operation will be rejected without having
any effect on system behaviour.
10
Press the green Reset
button.
All audible indicators
on all panels within
the operation zone of
the operator panel are
turned off.
Comments:
If there are no points signalling a fire alarm, the system is reset.
The red
FIRE
indicator goes off.
The red
Fire Brig. Signalled
indicator goes off.
The panel enters its idle state.
If there are points still
signalling an alarm when the
system is reset, go to the next
page.
SILENCE
Info : Completed
FIRE ALARMS
Total: 3
3 WORKSHOP
19:23
SILENCE
Info : Completed
FIRE ALARMS
Total: 3
3 WORKSHOP
19:23
1 OFFICES
2 CANTEEN
3 WORKSHOP
FIRE ALARMS
19:23
Total: 3
1: RESOUND
1 OFFICES
2 CANTEEN
3 WORKSHOP
FIRE ALARMS
19:23
Total: 3
1: RESOUND
RESET
Info : Completed
19:23
RESET
Info : Completed
19:23
AUTROSAFE
SelfVerify
AUTROSAFE
SelfVerify
www.ukpanels.com