System Menu
Operator's Handbook, AutroSafe Interactive Fire Alarm System, Release 3, ASAFE-FO/FE Rev. E, 021105,
Autronica Fire and Security AS
Page 81
13.8 How to Initialize the Fire Alarm System
The AutroSafe Interactive Fire Alarm System is automatically initialized
when the panel is turned on. However, in certain cases it may be
necessary to
manually
initialize the panel. In situations where the loop
topology has been changed in some way,
for example
, two detectors
have changed places or have been removed, a service command
(
Clear Topology
) has to be executed. When this command is
completed, the control panel has to be initialized manually.
The procedure below describes how to manually initialize the fire
alarm system.
Step
Actions to be taken
Display Indication
1
To enter the Main Menu, press
!
MENU
19:23
Total: 3
1 SHOW STATUS
2 DISABLE
3 ENABLE
4 SYSTEM
5 SERVICE
2
To select SYSTEM, press 4.
3
To select INITIALIZE, press 6.
4
To start the initialization, press
Comments:
The initializing procedure will start, and is
completed when the message «Completed» is
shown in the display. To return the System
Menu, press the Close button.
SYSTEM
1 DATE AND TIME
2 INFORMATION
3 ACCESS LEVEL 3
4 PRINTER
5 CHANGE LANGUAGE
6 INITIALIZE
7 DAY/NIGHT TIMERS
19:23
SYSTEM
1 DATE AND TIME
2 INFORMATION
3 ACCESS LEVEL 3
4 PRINTER
5 CHANGE LANGUAGE
6 INITIALIZE
7 DAY/NIGHT TIMERS
19:23
SYSTEM
INITIALIZE
Start INIT
Phase 1:
Phase 2:
Phase 3:
Phase 4:
Info: Completed
3 PAPER FEED
19:23
SYSTEM
INITIALIZE
Start INIT
Phase 1:
Phase 2:
Phase 3:
Phase 4:
Info:
3 PAPER FEED
19:23