Show Status
Operator's Handbook, AutroSafe Interactive Fire Alarm System, Release 3, ASAFE-FO/FE Rev. E, 021105,
Autronica Fire and Security AS
Page 54
10.4 Show Status – Fire Warnings
This menu gives detailed information on the current status of Fire
Warnings (Prealarms / Early Warnings) in the system. It provides the
following information:
•
the location
•
the exact time of activation
•
an identification of the detectors (address)
•
the type of detectors (optical, heat, etc.)
•
all detectors in Fire Warning
The
example
below describes how to view the current status of Fire
Warnings.
Step
Actions to be taken
Display Indication
1
To enter the Main Menu, press
!
MENU
19:23
Total: 3
1 SHOW STATUS
2 DISABLE
3 ENABLE
4 SYSTEM
5 SERVICE
2
To select SHOW STATUS, press 1.
SHOW STATUS
1 FIRE ALARMS
2 FIRE WARNINGS
3 FAULTS
4 DISABLEMENTS
5 DETECTION ZONES IN TEST
6 OIL&GAS INHIBITED POINTS
7 ACTIVATED OUTPUTS
19:23
3
To select FIRE WARNINGS, press 2.
4
To move the cursor to the desired selection,
scroll with the arrow buttons
6
PQR
or
9
YZ
5
To view detailed zonal information for the
selected detection zone, press
6
To view point(s) in Fire Warning for the selected
detection zone, press Action Digit 1 (SHOW
POINTS).
7
To return (each step backwards), press
www.ukpanels.com