Disabling
Operator's Handbook, AutroSafe Interactive Fire Alarm System, Release 3, ASAFE-FO/FE Rev. E, 021105,
Autronica Fire and Security AS
Page 63
11.3 Indications on the Operator Panel
When one or several disablements exist, the
Function
Disabled
indicator
on the Operator Panel will show a yellow steady light. The
panel’s display will indicate that a disablement exists (as shown in the
example below).
DISABLED DZs
1 CANTEEN
DISABLEMENTS
19:23
Total: 1
Total: 1
Figure 11-2: Disablement - indications on the display
11.4 Disabling Activated / Deactivated Components
When you disable an
active
component, for example, a sounder
issuing an alarm signal, the component will immediately switch to the
OFF state without any user notification and/or confirmation cause.
A disablement of a
deactivated
component, for example, a sounder
not issuing an alarm signal, will have no immediate effect on system
operation.
Both activated and deactivated disabled components will remain
switched off until enabled.
11.5 Disabling Detection Zones
When you disable a
Detection Zone
-
all
points within the specified
detection zone will be disabled. A detection zone will not be indicated
as disabled unless
all
points within the zone have been disabled.
A
disablement time
can be set. When the disablement time expires,
the detection zone will automatically be enabled. The detection zone
can also be enabled manually from the Enable Menu.
www.ukpanels.com