11.10 Disabling Fault Warning Routing Equipment
When you disable
Fault Warning Routing Equipment
(FWRE), the
output which controls such equipment will be disabled. In the event of
a fault, no fault warning signals will be sent to, for example, the
security firm.
A
disablement time
can be set. When the disablement time expires,
the Fault Warning Routing Equipment will automatically be enabled.
The equipment can also be enabled manually from the Enable Menu.
11.11 Disabling Immediate Output Actioning
In an alarm situation, the actioning of outputs in a Delayed Action
detection zone can be delayed (refer to
Delayed Action
detection
zones, page 26). To achieve a delay,
Immediate Output Actioning
must be disabled.
It is possible to disable immediate output actioning for
all Day / Night
areas
or for
selected Day / Night areas.
Note: A Day / Night area encompasses one or more detection zones
within the same operation zone.
The delay affects the actioning of outputs to Fire Alarm Devices (FAD),
Fire Alarm Routing Equipment (FARE) and/or Fire Protection
Equipment (FPE).
Note that an alarm from a
manual call-point
will normally (point delay
OFF) give immediate ouput actioning even though the immediate
output actioning has been disabled.
The function is useful in situations where you want to
disable
immediate output actioning
at special periods to avoid causing any
unnecessary disturbance.