Service Commands
Operator's Handbook, AutroSafe Interactive Fire Alarm System, Release 3, ASAFE-FO/FE Rev. E, 021105,
Autronica Fire and Security AS
Page 89
Step
Actions to be taken
Display Indication
7
To enter Test Mode for the selected zone (in this
example CANTEEN is chosen), press twice on
SERVICE
DZ TEST
1 ENTER TEST MODE
2 LEAVE TEST MODE
19:23
SERVICE
DZ TEST
1 ENTER TEST MODE
2 LEAVE TEST MODE
19:23
14.3.1.3 Leaving Test Mode
The procedure below describes how to leave test mode for a selected
zone (LEAVE TEST MODE).
Step
Actions to be taken
Display Indication
1
To enter the Main Menu, press
!
MENU
19:23
Total: 3
1 SHOW STATUS
2 DISABLE
3 ENABLE
4 SYSTEM
5 SERVICE
2
To select SERVICE, press 5.
SERVICE
19:23
1 TEST
2 LOG
3 LOOP COMMANDS
4 OIL&GAS INHIBIT
SERVICE
19:23
1 TEST
2 LOG
3 LOOP COMMANDS
4 OIL&GAS INHIBIT
3
To select TEST, press 1.
SERVICE
TEST
1 DETECTION ZONE TEST (EN 54)
2 OUTPUT TEST
3 OUTPUT CONTROL
19:23
SERVICE
TEST
1 DETECTION ZONE TEST (EN 54)
2 OUTPUT TEST
3 OUTPUT CONTROL
19:23