Service Commands
Operator's Handbook, AutroSafe Interactive Fire Alarm System, Release 3, ASAFE-FO/FE Rev. E, 021105,
Autronica Fire and Security AS
Page 90
Step
Actions to be taken
Display Indication
4
To select DETECTION ZONE TEST, press 1.
SERVICE
DZ TEST
1 ENTER TEST MODE
2 LEAVE TEST MODE
19:23
SERVICE
DZ TEST
1 ENTER TEST MODE
2 LEAVE TEST MODE
19:23
5
To select LEAVE TEST MODE, press 2.
(Only Detection Zones in Test Mode will appear
in the display).
SERVICE
19:23
LEAVE TEST MODE DZ
Zone Name:
CANTEEN
KITCHEN
OFFICES
WORKSHOP
SERVICE
19:23
LEAVE TEST MODE DZ
Zone Name:
CANTEEN
KITCHEN
OFFICES
WORKSHOP
6
Use the keyboard to enter text into the input box
-
OR
,- as shown in this example:
To select a Zone Name, press
then scroll downwards by pressing
9
YZ
or move up again by pressing
6
PQR
SERVICE
19:23
LEAVE TEST MODE DZ
Zone Name:
CANTEEN
KITCHEN
OFFICES
WORKSHOP
SERVICE
19:23
LEAVE TEST MODE DZ
Zone Name:
CANTEEN
KITCHEN
OFFICES
WORKSHOP
7
To leave Test Mode for the selected zone (in this
example CANTEEN is chosen), press twice on
SERVICE
DZ TEST
1 ENTER TEST MODE
2 LEAVE TEST MODE
19:23
SERVICE
DZ TEST
1 ENTER TEST MODE
2 LEAVE TEST MODE
19:23
www.ukpanels.com