Service Commands
Operator's Handbook, AutroSafe Interactive Fire Alarm System, Release 3, ASAFE-FO/FE Rev. E, 021105,
Autronica Fire and Security AS
Page 112
Step
Actions to be taken
Display Indication
3
To select LOOP COMMANDS, press 3.
SERVICE
19:23
LOOP COMMANDS
1 CLEAR TOPOLOGY
2 DISABLE LOOP
3 ENABLE LOOP
SERVICE
19:23
LOOP COMMANDS
1 CLEAR TOPOLOGY
2 DISABLE LOOP
3 ENABLE LOOP
4
To select CLEAR TOPOLOGY, press 1.
5
Use the keyboard to enter text into the input box
-
OR
,- as shown in this example:
To select the Loop Name, press
then scroll downwards by pressing
9
YZ
or move up again by pressing
6
PQR
6
To accept the selected Loop Name and clear the
topology for this Loop, press twice on
SERVICE
19:23
BSB 310
BSJ 310
BSL 310
CLEAR TOPOLOGY
Loop Name:
SERVICE
19:23
CLEAR TOPOLOGY
Loop Name:
BSB 310
BSJ 310
BSL 310
SERVICE
19:23
1 CLEAR TOPOLOGY