Operation Mode
Operator's Handbook, AutroSafe Interactive Fire Alarm System, Release 3, ASAFE-FO/FE Rev. E, 021105,
Autronica Fire and Security AS
Page 20
3.9 Resounding the Internal Buzzer
After pressing the MUTE PANEL button in an alarm condition, the
internal buzzer will automatically be resounded in the following cases:
•
if any
new
event occurs (for example, a detection zone enters the
Fire Alarm state)
•
after a timeout period if the cause for making it sound is still
present.
3.10 Resounding Fire Alarm Devices
When pressing the SILENCE ALARMS button in the event of an
alarm, all fire alarm devices (FAD) within the operation zone of the
operator panel will be deactivated. The red Fire Alarm indication lamp
will switch from blinking to steady light.
At this stage, the resound timer will start. The resound timer will restart
on each operation of the SILENCE ALARMS button.
To
manually
resound the alarm zones, Action Digit 1, which represents
RESOUND, can be pressed.
The alarm zones are
automatically
resounded to their alarm states on
timeout (configurable) of the SILENCE resound timer.
3.11 Resetting the System
In order to reset the system by pressing the RESET button, all Fire
Alarm Devices (FAD) have to be silenced / deactivated using the
SILENCE ALARMS button. Otherwise the reset operation will be
rejected without having any effect on system behaviour.
www.ukpanels.com