GS1 Series AC Drive User Manual
4–15
Chapter 4: AC Drive Parameters
Skip Frequency 1
Mem Addr 010AH(40267)
Range: 0.0 to 400.0Hz
Default Setting: 0.0
Skip Frequency 2
Mem Addr 010BH(40268)
Range: 0.0 to 400.0Hz
Default Setting: 0.0
Skip Frequency 3
Mem Addr 010CH(40269)
Range: 0.0 to 400.0 Hz
Default Setting: 0.0
• 1-10, 1-11, and 1-12 determine the location of the frequency bands that will be
skipped during AC drive operation.
Skip Frequency Band
Mem Addr 0111H(40274)
Range: 0.0 to 20.0 Hz
Default Setting: 0.0
•This parameter determines the frequency band for a given Skip Frequency (1-10, 1-
11, or 1-12). Half of the Skip Frequency Band is above the Skip Frequency and the
other half is below. Programming this parameter to 0.0 disables all skip
frequencies.
1-17
1-12
1-11
1-10
Output frequency
Skip Frequency 1
1-10
Skip Frequency 2
1-11
Skip Frequency 3
1-12
Skip Frequency
Set Point
Skip Frequency Band
1-17