GS1 Series AC Drive User Manual
3–7
Chapter 3: Keypad Operation and Quickstart
Acceleration Time
Setting: 5.0
Range: 0.1 to 600 sec
Default Setting: 10 sec
The motor should accelerate from 0 RPM to Base RPM (0-03) in 5
seconds.
Deceleration Time
Setting: 5.0
Range: 0.1 to 600 sec
Default Setting: 30 sec
The motor should decelerate from Maximum RPM (0-04) to 0 RPM in
5 seconds.
Volts/Hertz Settings
Setting: 1
Range: 0 - General Purpose
Default Setting: 0
1 - High Starting Torque
2 - Fans and Pumps
3 - Custom
The GS1 Series AC drive has some predefined torque settings that meet
the needs of most applications. A custom setting is available if needed.
In this example, the application requires a high starting torque.
Source of Operation Command
Setting: 2
Default Setting: 0
Settings
0
Operation Determined by Digital Keypad
1
Operation determined by external control
terminals. Keypad STOP is enabled.
2
Operation determined by external control
terminals. Keypad STOP is disabled.
3
Operation determined by RS485 interface.
Keypad STOP is enabled.
4
Operation determined by RS485 interface.
Keypad STOP is disabled.
The AC drive operation will be determined by external control
terminals and the keypad stop will be disabled.
3-00
2-00
1-02
1-01