Detailed Parameter Listings
Note: If the
symbol is found next to the parameter name, the parameter can be
edited when the AC drive is in RUN Mode.
Motor Parameters
Motor Nameplate Voltage
Mem Addr: 0000H(40001)
Range: 200V series: 200/208/220/230/240
Default Setting: 240
•This parameter determines the Maximum Output Voltage of the AC drive. The
Maximum Output Voltage setting must be less than or equal to the rated voltage of the
motor as indicated on the motor nameplate. The setting value must be equal to or
greater than the Mid-Point Voltage (2-05).
Motor Nameplate Amps
Mem Addr: 0001H(40002)
Range: Drive Rated Amps x 0.3 to
Default Setting: Drive Rating (A)
Drive Rated Amps x 1.0
•This parameter sets the output current to the motor. The value is determined by
the value found on the motor nameplate.
0-01
0-00
Motor Nameplate Voltage
Mem Addr: 0000H (40001)
Range: 200V series: 200/208/220/230/240
Default Setting: 240
•This parameter determines the Maximum Output Voltage of the AC drive. The Maximum Output
Voltage setting must be less than or equal to the rated voltage of the motor as indicated on the motor
nameplate. The setting value must be equal to or greater than the Mid-Point Voltage (2-05).
0-00
Parameter
Number
Parameter Setting
Range
Parameter
Description
Parameter Default
Setting
Parameter
Name
Parameter Memory Address
Hexadecimal (Decimal)
GS1 Series AC Drive User Manual
4–9
Chapter 4: AC Drive Parameters
Содержание GS1-10P2
Страница 1: ...GS1 Series Drives U s e r M a n u a l 120V Input 0 25 0 5 Hp 230V Input 0 25 2 0 Hp...
Страница 15: ......
Страница 117: ......
Страница 123: ......
Страница 137: ...GS1 M...