Transmission Fault Treatment
Mem Addr 0903H(42308)
Default Setting: 0
Setting:
0 - Display fault and continue operating
1 - Display fault and RAMP to stop
2 - Display fault and COAST to stop
3 - No fault displayed and continue operating
Time Out Detection
Mem Addr 0904H(42309)
Range: 0 - Disable
Default Setting: 0
1 - Enable
•This parameter is used for ASCII mode. When this parameter is set to
01, it indicates that the over-time detection is enabled and the time slot between
each character cannot exceed 500 ms.
Time Out Duration
Mem Addr 0905H(42310)
Range: 0.1 to 60.0 seconds
Default Setting: 0.5
Parameter Lock
Mem Addr 0907H(42312)
Range: 0 - All parameters can be set and read
Default setting: 0
1 - All parameters are read-only
Restore to Default
Mem Addr 0908H(42313)
Range: 0 to 99
Default Setting: 0
• Setting 99 restores all parameters to factory defaults.
Block Transfer Parameter 1
Mem Addr 090BH(42316)
Range: 0-00 to 8-01, and 9-99
Default Setting: 9-99
• Setting 9-99 disables the parameter.
Block Transfer Parameter 2
Mem Addr 090CH(42317)
Range: 0-00 to 8-01, and 9-99
Default Setting: 9-99
• Setting 9-99 disables the parameter.
9-12
9-11
9-08
9-07
9-05
9-04
9-03
GS1 Series AC Drive User Manual
4–47
Chapter 4: AC Drive Parameters