Chapter 3: Keypad Operation and Quickstart
GS1 Series AC Drive User Manual
3–6
Parameter Setup
In order to meet the needs of this application, the parameters should be set as follows:
Motor Nameplate Voltage
Setting: 230
Range: 200V series: 200/208/220/230/240
Default Setting: 240
This parameter setting is determined by the motor nameplate.
Motor Nameplate Amps
Setting: 4.2
Range: Drive Rated Amps x .3 to
Default Setting: Drive Rating (A)
Drive Rated Amps x 1.0
This parameter setting is determined by the motor nameplate..
Motor Base Frequency
Setting: 60
Range: 50/60/400
Default Setting 60
This parameter setting is determined by the motor nameplate.
Motor Base RPM
Setting: 1725
Range: 375 to 9999 RPM
Default Setting: 1750
This parameter setting is determined by the motor nameplate.
Motor Maximum RPM
Setting: 2000
Range:
0-03
to 9999 RPM
Default Setting:
0-03
This parameter setting is determined by the needs of the application.
W
ARNING
: The Motor Maximum RPM parameter (0-04) should never exceed the
maximum RPM rating for the motor you are using. If this information is not readily
available, consult your motor manufacturer.
Stop Methods
Setting: 0
Range: 0 - Ramp to Stop
Default Setting: 0
1 - Coast to stop
The application requires that this parameter be set to Ramp to Stop
because the motor needs to stop under power. If the AC drive was set for
Coast to Stop, the AC drive would ignore the Deceleration Time setting.
W
ARNING
: If the Stop Method for the GS1 AC drive is set for Coast to Stop, the AC
drive will ignore any setting you have for Deceleration Time (1-02).
1-00
0-04
0-03
0-02
0-01
0-00