GS1 Series AC Drive User Manual
1–7
Chapter 1: Getting Started
General Specifications (cont.)
Protective Functions
Overcurrent, Overvoltage, Undervoltage, Electronic thermal
motor overload, Overheating, Overload, Self testing
Operator
Interface
Operator Devices
5-key, 4-digit, 7-segment LED, 4 status LEDs, potentiometer
Programming
Parameter values for setup and review, fault codes
Parameter Monitor
Master Frequency, Output Frequency, Scaled Output Frequency,
Output Voltage, DC Bus Voltage, Output Direction, Trip Event
Monitor, Trip History Monitor
Key Functions
RUN/STOP, DISPLAY/RESET, PROGRAM/ENTER, <UP>,
<DOWN>
Environment
Enclosure Rating
Protected chassis, IP20
Ambient Temperature
-10° to 40°C (14°F to 104°F) w/o derating
Storage Temperature
-20° to 60 ° C (-4°F to 140°F) during short-term transportation
period)
Ambient Humidity
0 to 90% RH (non-condensing)
Vibration
9.8 m/s2(1G), less than 10Hz. 5.88 m/s2 (0.6G) 20 to 50 Hz
Installation Location
Altitude 1000m or lower above sea level, keep from corrosive
gas, liquid and dust