Chapter 4: AC Drive Parameters
GS1 Series AC Drive User Manual
4–12
Deceleration Time 1
Mem Addr: 0102H(40259)
Range: 0.1 to 600.0 sec
Default Setting: 30.0 sec
•This parameter is used to determine the time required for the AC drive to decelerate
from the Maximum Motor RPM (0-04) down to 0Hz. The rate is linear unless S-Curve is
“Enabled.”
Accel S-Curve
Mem Addr: 0103H(40260)
Range: 0 to 7
Default Setting: 0
•This parameter is used whenever the motor and load need to be accelerated more
smoothly. The Accel S-Curve may be set from 0 to 7 to select the desired
acceleration S Curve.
1-03
1-02
Decel Time
1 or 2
Accel Time
1 or 2
S-curve
characteristics
Time
S-curve
characteristics
Time
Time
Time
Frequency
1-03 = 0
"Accel S curve Disabled"
1-04 = 0
"Decel S curve Disabled"
Содержание GS1-10P2
Страница 1: ...GS1 Series Drives U s e r M a n u a l 120V Input 0 25 0 5 Hp 230V Input 0 25 2 0 Hp...
Страница 15: ......
Страница 117: ......
Страница 123: ......
Страница 137: ...GS1 M...