Chapter 4: AC Drive Parameters
GS1 Series AC Drive User Manual
4–22
Setting Explanations for parameters 3-02 and 3-03
Setting 0: External Fault (N.O.)
When an External Fault input signal is received, the AC drive output will turn off,
the drive will display “
EF
” on the LED Display, and the motor will Coast to
Stop.To resume normal operation, the external fault must be cleared, and the drive
must be reset.
Setting 1: External Fault (N.C.)
Setting 2: External Reset
An External Reset has the same function as the Reset key on the digital keypad.
Use an External Reset to reset the drive after a fault.
DI3-DI4: External Fault (N.O.)
"Close": Drive receives external fault input signal
DI3-DI4
CM
External Fault (N.O)
DI3-DI4: External Fault (N.C.)
"Open": Drive receives external fault input signal
DI3-DI4
CM
External Fault (N.C)
DI3-DI4: External Reset
"Close": Drive receives external reset input signal
DI3-DI4
CM
External Reset