Features and functions
●
6 programmable output contacts:
-
5 potential-free NO contacts with one common, max. 250 V AC, 1 A (resistive
load)
Default configuration: End position CLOSED, end position OPEN, selector switch
REMOTE, torque fault CLOSE, torque fault OPEN
-
1 potential-free change-over contact, max. 250 V AC, 5 A (resistive load)
Default configuration: Collective fault signal (torque fault, phase failure, motor
protection tripped)
●
Analogue output signal for position feedback
-
Galvanically isolated position feedback 0/4 – 20 mA (load max. 500
Ω
)
Standard:
Status signals
(output signals)
●
6 programmable output contacts:
-
5 change-over contacts with one common, max. 250 V AC, 1 A (resistive load),
1 potential-free change-over contact, max. 250 V AC, 5 A (resistive load)
●
12 programmable output contacts:
-
10 potential-free NO contacts, 5 with one common each, max. 250 V AC, 1 A
(resistive load), 2 potential-free change-over contacts, max. 250 V AC, 5 A (resistive
load)
●
6 programmable output contacts:
-
6 potential-free change-over contacts without one common, per contact max. 250
V AC, 5 A (resistive load)
●
10 programmable output contacts:
-
10 potential-free change-over contacts without one common, per contact max.
250 V AC, 5 A (resistive load)
●
6 programmable output contacts:
-
4 mains failure proof potential-free NO contacts with one common, max. 250 V
AC, 1 A (resistive load), 1 potential-free NO contact, max. 250 V AC, 1 A (resistive
load), 1 potential-free change-over contact, max. 250 V AC, 5 A (resistive load)
●
6 programmable output contacts:
-
4 mains failure proof potential-free NO contacts, max. 250 V AC, 5 A (resistive
load), 2 potential-free change-over contacts, max. 250 V AC, 5 A (resistive load),
●
12 programmable output contacts:
-
8 mains failure proof potential-free NO contacts, max. 250 V AC, 1 A (resistive
load), 2 potential-free NO contacts, max. 250 V AC, 1 A (resistive load), 2 potential-
free change-over contacts, max. 250 V AC, 5 A (resistive load)
●
12 programmable output contacts:
-
8 mains failure proof potential-free NO contacts, max. 250 V AC, 5 A (resistive
load), 4 potential-free change-over contacts, max. 250 V AC, 5 A (resistive load),
All output signals must be supplied with the same potential.
Options:
Auxiliary voltage 24 V DC: max. 100 mA for supply of control inputs, galvanically isolated
from internal voltage supply.
Standard:
Voltage output
Auxiliary voltage 115 V AC: max. 30 mA for supply of control inputs, galvanically isolated
from internal voltage supply
Option:
2 analogue outputs:
With position transmitter option: Output of travel, torque or output speed as continuous values between
0/4 and 20 mA
Analogue output (option)
2 analogue inputs:
With positioner/process controller option: Input of actual position value/actual process value as continuous
values between 0/4 and 20 mA
Analogue input (option)
●
Selector switch: LOCAL - OFF - REMOTE (lockable in all three positions)
●
Push buttons: OPEN, STOP, CLOSE, RESET
-
Local STOP
The actuator can be stopped via push button STOP of local controls if the selector
switch is in position REMOTE. (Not activated when leaving the factory.)
●
6 indication lights:
-
Running indication CW (yellow), torque fault CLOSE (red), motor protection tripped
(red), torque fault CCW (red), running indication CCW (green), Bluetooth (blue)
●
Graphic LC display: illuminated
Standard:
Local controls
●
Special colours for the indication lights:
-
Running indication CW (green), torque fault CLOSE (blue), torque fault OPEN
(yellow), motor protection tripped (violet), running indication CCW (red)
Option:
85
SAVEx 07.2 – SAVEx16.2/SARVEx 07.2 – SARVEx16.2 Control unit: electronic (MWG)
ACVExC 01.2 Non-Intrusive
Technical data