Figure 75: Signal behaviour of positions
Information
The set signal behaviour is valid for all positions.
10.1.12. Hysteresis for signalling intermediate positions: set
The hysteresis determines the tripping point.
Example
Parameter
Position 4 M1153
is set to 180° (50 % of the travel).
Parameter
Hysteresis M1148
is set to 3.0°.
Figure 76: Switching behaviour for signalling behaviours B, C, D and hysteresis 3.0°.
P1
Switch-on point (
●
)
P2
Switch-off point (
○
)
pT
Pulse duration = 2 times XT + hysteresis
Required user level:
AUMA (6)
.
Customer settings M0041
Multiport valve M1140
Hysteresis M1148
Default values:
0.5°
for all 16 intermediate positions
Setting range:
0.0°
to
5.0°
(degree)
10.2.
Torque switching: set
Once the set torque is reached, the torque switches will be tripped (overload protection
of the valve).
Information
The torque switches may also trip during manual operation.
66
SAVEx 07.2 – SAVEx16.2/SARVEx 07.2 – SARVEx16.2 Control unit: electronic (MWG)
Commissioning (basic settings)
ACVExC 01.2 Non-Intrusive