![AUMA SARVEx 07.2 Скачать руководство пользователя страница 84](http://html1.mh-extra.com/html/auma/sarvex-07-2/sarvex-07-2_operation-instructions-manual_3016487084.webp)
13.2.
Technical data Actuator controls
Features and functions
Refer to name plate
Explosion protection
Certificates are attached to the device. All standards applied and their respective issues are indicated
on these certificates.
Certificates and standards
The particular conditions of use are listed on the certificates supplied.
Particular conditions of use
Standard voltages AC:
1-phase AC
Voltages/frequencies
3-phase AC
Voltages/frequencies
220 – 240
110 – 120
Volt
380 – 480
220 – 240
Volt
60
50
60
50
Hz
60
50
60
50
Hz
Permissible variation of mains frequency:
±
5 %
Permissible variation of mains voltage:
±
10 %
–30 % for maximum 10 seconds within a range of 380 V – 480 V with the following restrictions:
●
If required, the motor speed will be reduced down to nominal speed depending on the load of the
actuators used
●
A low mains voltage increases the mains current consumption; a higher mains voltage reduces the
mains current consumption
●
The torque limits of the actuators used might be decreased for a short time, if applicable
Power supply
24 V DC: +20 % / –15 %
Current consumption: Basic version approx. 250 mA, with options up to 500 mA
For external electronics supply, the power supply of integral controls must have an enhanced isolation
against mains voltage in compliance with IEC 61010-1 and the output power be limited to 150 VA.
External supply of the electronics
(option)
The actuator controls are designed for the rated power motor power, refer to motor name plate
Rated power
6 digital inputs: OPEN, STOP, CLOSE, EMERGENCY (via opto-isolator, thereof OPEN, STOP, CLOSE
with one common and EMERGENCY without common, respect minimum pulse duration for modulating
actuators.
Control inputs
24 V DC, current consumption: approx. 10 mA per input
Standard
Control voltage/current consumption
for control inputs
48 V DC, current consumption: approx. 7 mA per input
60 V DC, current consumption: approx. 9 mA per input
100 V – 125 V DC, current consumption: approx. 15 mA per input
100 V – 120 V AC, current consumption: approx. 15 mA per input
Options:
All input signals must be supplied with the same potential.
84
SAVEx 07.2 – SAVEx16.2/SARVEx 07.2 – SARVEx16.2 Control unit: electronic (MWG)
Technical data
ACVExC 01.2 Non-Intrusive