2.
Return to the main menu and select the simulation value in parameter
TMS
proof test M1950
: Select
Thermal test
.
3.
Activate motor protection simulation: Press
Ok
push button.
The safety function is correct if no fault signal is displayed.
4.
Reset simulation: Press
Ok
push button or exit the simulation menu and reset
the selector switch to its initial position.
76
SAVEx 07.2 – SAVEx16.2/SARVEx 07.2 – SARVEx16.2 Control unit: electronic (MWG)
Corrective action
ACVExC 01.2 Non-Intrusive