Valve damage due to excessive tripping torque limit setting!
→
The tripping torque must suit the valve.
→
Only change the setting with the consent of the valve manufacturer.
Customer settings M0041
Torque switching M0013
Trip torque CLOSE M0088
Trip torque OPEN M0089
Default value: According to order data
Setting range: Torque range according to actuator name plate
Select main menu
1.
Set selector switch to position 0 (OFF).
2.
Press push button C
Setup
and hold it down for approx. 3 seconds.
➥
Display goes to main menu and indicates:
▶ Display
Select parameter
3.
Select parameter either:
→
click via the menu
to parameter, or
→
via direct display: press and enter ID
M0088
.
➥
Display indicates:
Trip torque CLOSE
CLOSE or OPEN
4.
Use
Up ▲ Down ▼
to select:
→
▶ Trip torque CLOSE
→
▶ Trip torque OPEN
➥
The black triangle
▶
indicates the current selection.
5.
Press
Ok
.
➥
Display shows the set value.
➥
The bottom row indicates:
Edit Esc
6.
Press
Edit
.
➥
Display indicates:
-
Specialist (4) →
continue with step 7
-
in bottom row
Up ▲ Down ▼ Esc →
continue with step 11
User login
7.
Use
Up ▲ Down ▼
to select user:
Information: Required user level:
Specialist (4)
or higher.
➥
The symbols have the following meanings:
-
black triangle:
▶
= current setting
-
white triangle:
▷
= selection (not saved yet)
8.
Press
Ok
.
➥
Display indicates:
Password 0***
9.
Enter password (
→
enter password).
➥
Display shows the set value.
➥
The bottom row indicates:
Edit Esc
10.
Press
Edit
.
Change value
11. Enter new value for tripping torque via
Up ▲ Down ▼
.
Information: The adjustable torque range is shown in round brackets.
67
SAVEx 07.2 – SAVEx16.2/SARVEx 07.2 – SARVEx16.2 Control unit: electronic (MWG)
ACVExC 01.2 Non-Intrusive
Commissioning (basic settings)