Symbol
Set positions (of valve ports)
(P1, P2, ...) selected position (1, 2, ...)
P
No position has been selected.
– – / –N/A–
Actual position value
E2
Homeport (zero point) set
No homeport (zero point) has been set
To interrupt an operation (triggered operation command):
→
Select “– – / –N/A–” during operation and confirm via
Ok
(push button ). The
actuator stops in its current position.
10.1.7.
Operate to position from Remote
For direct operation to position from remote, make sure that selector switch position
Remote control (REMOTE) is selected.
Operation to position via digital inputs
An input (DIN) must be configured for each position (valve port).
Configuration of digital inputs
Required user level:
Specialist (4)
or higher.
Device configuration M0053
I/O interface M0139
Digital inputs M0116
Example
DIN4 input to operate to position 1 selecting the shortest path:
Parameters:
Signal DIN 4 M0118
=
Intermediate pos. 1
Operation behaviour for input control
Setting values for digital inputs (DIN)
Operation to defined position while selecting the
shortest path
Intermediate pos. 1
to
Intermediate pos. 16
Operation to defined position in clockwise direction
MPV: CW Position 1
to
MPV: CW Position 10
Operation to defined position in counterclockwise
direction
MPV: CCW Position 1
to
MPV: CCW Position 10
Actuator operates in clockwise direction (without
stop at any position).
MPV DriveCW
Actuator operation in counterclockwise direction
(without stop at any position).
MPV DriveCCW
Command “Next position”
Required user level:
Specialist (4)
or higher.
A digital input is used to select the desired operation to the next port including the
direction of operation. Thus, up to 16 ports can be approached in both directions,
even without fieldbus connection with only 2 inputs.
Device configuration M0053
I/O interface M0139
Digital inputs M0116
Example
Parameter
Signal DIN 1 M0117
:
●
Next position CW
= clockwise
●
Next position CCW
= counterclockwise
Self-retaining when leaving the factory in both direction (cw and ccw).
64
SAVEx 07.2 – SAVEx16.2/SARVEx 07.2 – SARVEx16.2 Control unit: electronic (MWG)
Commissioning (basic settings)