9.
Signals (output signals)
9.1.
Status signals via output contacts (digital outputs)
Characteristics
Output contacts are used to send status signals (e.g. reaching the end positions,
selector switch position, faults...) as binary signals to the control room.
Status signals only have two states: active or inactive. Active means that the
conditions for the signal are fulfilled.
9.1.1.
Assignment of outputs
The output contacts (outputs DOUT 1 – 12) can be assigned to various signals.
Required user level:
Specialist (4)
or higher.
Device configuration M0053
I/O interface M0139
Digital outputs M0110
Signal DOUT 1 M0109
Table 25: Default values
Default value:
Output
Default value:
Output
Thermal fault
Signal DOUT 7
Fault
Signal DOUT 1
OPEN
Signal DOUT 8
End position
CLOSED
Signal DOUT 2
Limit switch CLOSED
Signal DOUT 9
End position
OPEN
Signal DOUT 3
Limit switch OPEN
Signal DOUT 10
Selector sw. RE-
MOTE
Signal DOUT 4
Torque sw. CLOSED
Signal DOUT 11
Torque fault
CLOSE
Signal DOUT 5
Torque sw. OPEN
Signal DOUT 12
Torque fault
OPEN
Signal DOUT 6
9.1.2.
Coding the outputs
The output signals
Coding DOUT 1
–
Coding DOUT 12
can be set either to high
active or low active.
●
High active = output contact closed = signal active
●
Low active = output contact open = signal active
Signal active means that the conditions for the signal are fulfilled.
Required user level:
Specialist (4)
or higher.
Device configuration M0053
I/O interface M0139
Digital outputs M0110
Coding DOUT 1 M0102
Default values:
Coding DOUT 1
=
Low active
Coding DOUT 2
–
Coding DOUT 12
=
High active
9.2.
Analogue signals (analogue outputs)
Valve position
Signal: E2 = 0/4 – 20 mA (galvanically isolated)
Designation in the wiring diagram: AOUT1 (position)
Torque feedback
Signal: E6 = 0/4 – 20 mA (galvanically isolated)
Designation in the wiring diagram: AOUT2 (torque)
For further information on this topic, please refer to Manual (Operation and setting).
59
SAVEx 07.2 – SAVEx16.2/SARVEx 07.2 – SARVEx16.2 Control unit: electronic (MWG)
ACVExC 01.2 Non-Intrusive
Signals (output signals)