Activate/deactivate signal via DIP switch [S2].
Figure 55:
DIP switch on logic board
[S2]
6-way DIP, switch 6
➥
Switch 6 in lower position (position ON): The signal "Torque fault in collective
fault signal" is activated.
➥
Switch 6 in upper position (position OFF): The signal "Torque fault in collective
fault signal" is deactivated.
10.6
Positioner
— (Option) —
→
Prior to positioner setting, set limit and torque switching as well as potentiometer
or electronic position transmitter.
10.6.1
Input ranges (signal type) for setpoint and actual value
The input range (signal type) for setpoint E1 and actuator value E2 is set in the
factory and marked with a label on the cover plate of the positioner.
The type of signal can be modified at a later date exclusively for versions with setpoint
E1
≠
0/4 – 20 mA and split-range version. For these versions, the positioner board
is equipped with an additional contact.
Figure 56:
Version with additional switch on the positioner board
5.
Label indicating the set input ranges
[S1-7] 5 contact DIP switch for setting
DIP1 Actual value E2 (current or voltage signal)
DIP3 Setpoint E1 (current or voltage signal)
DIP5 Setpoint E1 (double signal range e.g. for split range)
44
SAExC 07.1 – SAExC 16.1/SARExC 07.1 – SARExC 16.1
Commissioning – controls settings