For the connection of remote position transmitters, screened cables must be
used.
Type of current, mains
voltage and mains fre-
quency
Type of current, mains voltage and mains frequency must match the data on the
motor name plate.
Figure 13:
Motor name plate (example)
[1]
Type of current
[2]
Mains voltage
[3]
Mains frequency (for 3-ph and 1-ph AC motors)
Connecting cables
●
For device insulation, appropriate (voltage-proof) cables must be used. Specify
cables for the highest occurring rated voltage.
●
Use connecting cables with a minimum temperature range of +80 °C.
●
For connecting cables exposed to UV radiation (outdoor installation), use UV
resistant cables.
5.2
Connecting via plug/socket connector with screw-type terminals (KP, KPH)
5.2.1
Terminal compartment: open
Figure 14:
Plug/socket connector KPH, KP
[1]
Cover
[2]
Screws for cover
[3]
O-ring
[4]
Terminal compartment
[5]
Terminal board
18
SAExC 07.1 – SAExC 16.1/SARExC 07.1 – SARExC 16.1
Electrical connection
AMExB 01.1