9.
Commissioning (basic settings)
1.
Set selector switch to position 0 (OFF).
Information: The selector switch is not a mains switch. When positioned to 0
(OFF), the actuator cannot be operated. The controls' power supply is
maintained.
2.
Switch on the power supply.
Information: Please consider the heat-up time for ambient temperatures below
–20 °C.
3.
Perform basic settings.
9.1
Heat-up time for low temperature version
Please note that for low temperature versions, the controls require a heat-up time.
This heat-up time is applicable in case the actuator and the controls are not live and
have cooled down to ambient temperature. Under these conditions and after
connection to the voltage supply, the following heat-up times must be complied with
prior to commissioning:
For –50 °C = 60 min.
For –60 °C = 80 min.
Figure 34:
Sketch illustrating the heat-up time
[t ]
Heat-up time in minutes
[
ϑ
]
Ambient temperature in °C
9.2
Switch compartment: open
The switch compartment must be opened to perform the following settings (options).
31
SAExC 07.1 – SAExC 16.1/SARExC 07.1 – SARExC 16.1
AMExB 01.1
Commissioning (basic settings)