Table 10:
Recommended settings
[S2–7]
Signal type
Behaviour on loss of signal of
DIP 1 2 3 4
Actual value E2
Setpoint E1
E1 and/or E2
4 – 20 mA
4 – 20 mA
Fail as is
Fail close
Fail open
Table 11:
Further possible settings
[S2–7]
Signal type
1)
Behaviour on loss of signal of
DIP 1 2 3 4
Actual value E2
Setpoint E1
E2
E1
0 – 5 V
4 – 20 mA
Fail open
Fail as is
0 – 5 V
4 – 20 mA
Fail open
Fail close
4 – 20 mA
0 – 20 mA
0 – 20 mA
0 – 5 V
0 – 20 mA
0 – 5 V
0 – 10 V
4 – 20 mA
0 – 20 mA
0 – 5 V
Fail close
4 – 20 mA
0 – 20 mA
0 – 10 V
Fail as is
0 – 20 mA
0 – 5 V
4 – 20 mA
Fail open
in case of a signal loss, a misinterpretation might be made for 0 – 20 mA, 0 – 5 V or 0 – 10 V, due
to the fact that E1 or E2 could take the value 0 mA even without loss of signal (end position CLOSED
= 0 mA or 0 V).
1)
10.6.3
Adjustment in end positions
The setting described below applies to the standard positioner version, i.e. maximum
setpoint E1 (20 mA) triggers a travel to end position OPEN, minimum setpoint (0/4
mA) triggers a travel to end position CLOSED.
46
SAExC 07.1 – SAExC 16.1/SARExC 07.1 – SARExC 16.1
Commissioning – controls settings
AMExB 01.1