Standard:
●
Switch-off mode adjustable
-
Limit or torque seating for end position OPEN and end position CLOSED
●
Overload protection against excessive torques over the whole travel
●
Excessive torque (torque fault) can be excluded from collective fault signal.
●
Phase failure monitoring with automatic phase correction
●
Push-to-run operation or self-retaining in REMOTE
●
Push-to-run operation or self-retaining in LOCAL
●
Running indication via blinker transmitter signal of actuator (option) can be activated or
deactivated
Options:
●
Positioner
-
Position setpoint via analogue input E1 = 0/4 – 20 mA
-
Galvanic isolation for position setpoint (0/4 – 20 mA) and position feedback (0/4 – 20
mA)
-
Adjustable behaviour on loss of signal
-
Adjustable sensitivity (dead band) and pause time
●
Positioner for Split Range operation
Functions
Standard:
Monitoring of the motor temperature with PTC tripping device in combination with PTC ther-
mistors in the actuator motor
Options:
Thermal overload relay in combination with thermoswitches in the actuator motor
Motor protection evaluation
Standard:
Plug/socket connector with screw type terminals (KP, KPH) Ex e (increased safety) and M-
threads
Options:
●
Plug/socket connector with terminal blocks (KES) Ex e (increased safety)
●
Plug/socket connector with terminal blocks (KES) Ex d (flameproof enclosure)
●
Pg-threads, NPT-threads, G-threads, special threads
●
Parking frame for wall mounting of the disconnected plug
●
Protection cover for plug compartment (when plug is removed)
Electrical connection
Refer to name plate
Wiring diagram
The reversing contactors are designed for a lifetime of 2 million starts.
1)
Not possible in combination with PTC tripping device
2)
13.3
Service conditions
Any position
Mounting position
Indoor and outdoor use permissible
Use
Standard:
●
IP 67 with AUMA 3-ph AC motor
For both enclosure protection types (IP 67 and IP 68), the terminal compartment is additio-
nally sealed against the interior – double sealed
For actual version, refer to actuator/controls name plate.
Enclosure protection according
to EN 60529
Standard:
KS: Suitable for installation in industrial units, in water or power plants with a low pollutant
concentration as well as for installation in occasionally or permanently aggressive atmosphere
with a moderate pollutant concentration (e.g. in wastewater treatment plants, chemical indus-
try)
Options:
●
KX: Suitable for installation in extremely aggressive atmospheres with high humidity and
high pollutant concentration
●
KX-G : same as KX, however aluminium-free version (outer parts)
Corrosion protection
Standard:
≤
2,000 m above sea level
Option: > 2,000 m above sea level, please contact AUMA
Installation altitude
Standard: Paint based on polyurethane (powder coating)
Finish coating
Standard: AUMA silver-grey (similar to RAL 7037)
Colour
60
SAExC 07.1 – SAExC 16.1/SARExC 07.1 – SARExC 16.1
Technical data
AMExB 01.1