Information
If the maximum value cannot be reached, the selection of the reduction gearing must
be checked. (The max. possible turns/stroke are indicated on the order-related
technical data sheet for the actuator.)
9.9
Mechanical position indicator: set
— Option —
1.
Place indicator disc on shaft.
2.
Move valve to end position CLOSED.
3.
Turn lower indicator disc until symbol
(CLOSED) is in alignment with the
mark on the cover.
4.
Move actuator to end position OPEN.
5.
Hold lower indicator disc in position and turn upper disc with symbol
(OPEN)
until it is in alignment with the mark on the cover.
6.
Move valve to end position CLOSED again.
7.
Check settings:
If the symbol
(CLOSED) is no longer in alignment with mark on the cover:
7.1 Repeat setting procedure.
7.2 Check whether the appropriate reduction gearing has been selected, if
required.
9.10
Switch compartment: close
Danger of corrosion due to damage to paint finish!
→
Touch up damage to paint finish after work on the device.
1.
Clean sealing faces of housing and cover.
2.
Preserve joint surfaces with an acid-free corrosion protection agent.
3.
Check whether O-ring [3] is in good condition, replace if damaged.
39