Table 8:
Input range setting for setpoint E1
[S1–7]
Setpoint E1
DIP 3 and 5
0/4 – 20 mA
0 – 5 V
0 – 10 V
Table 9:
Input range setting for actual value E2
[S1–7]
Actual value E2
DIP 1
0/4 – 20 mA
1)
0 – 5 V
2)
for internal feedback of electronic position transmitter RWG
1)
for internal feedback of precision potentiometer 5 k
Ω
2)
Information
When changing the setting, a new label [5] indicating the set signal type must be
provided. Furthermore, the wiring diagram indicated on the name plate of the actuator
controls also changes.
10.6.2
Behaviour on loss of signal (actuator reaction)
In case of a loss of signal of setpoint E1 or actual value E2, the reaction of the actuator
can be programmed via switch [S2-7]. The complete selection range, however, is
only available for signals 4 – 20 mA.
The following reactions are possible:
Fail as is:
Actuator stops immediately and remains in this position.
Fail close:
Actuator moves the valve to end position CLOSED.
Fail open:
Actuator moves the valve to end position OPEN.
Figure 57:
DIP switch [S2-7] on positioner board
DIP1 = ON, actual value E2 is monitored
DIP2 = ON, setpoint E1 is monitored
45
SAExC 07.1 – SAExC 16.1/SARExC 07.1 – SARExC 16.1
AMExB 01.1
Commissioning – controls settings