7.13.4 Operating time monitoring
This function allows the monitoring of the operating time of the actuator. If
the actuator needs longer than the set time (
MAX. RUN TIME
parameter)
to move from end position OPEN to end position CLOSED, the following
warning signals are given (the actuator is not stopped):
.
Status indication
S0
: operation mode OFF/LOCAL =
WRN + NR
.
Status indication
S0/S6
: operation mode REMOTE =
WARNING IND.
.
Status indication
S2
:
WARNING OPER. TIME
The warning signals are automatically cleared when a new operation com-
mand is executed.
When the actuator moves from an intermediate position to an end position,
the set monitoring time for the whole stroke is assigned in relation to the
remaining stroke/travel.
Switching the operating time monitoring on/off
Information
This parameter is also used to switch the monitoring of the max. number of
starts per hour and the max. running time per hour (page 67) on/off.
Æ
Via the menu to parameter:
MAIN MENU (M0)
CONFIGURATION (M4)
SPECIAL FUNCTIONS (M40)
MONITOR TRIGGERS (M4016)
Default value:
FUNCTION ACTIVE
È
Description of the parameter settings:
FUNCTION NOT ACTIVE
The operating time monitoring is switched off.
FUNCTION ACTIVE
The operating time monitoring is switched on.
Setting the max. permissible operating time
Æ
Via the menu to parameter:
MAIN MENU (M0)
SETTINGS (M1)
MONITOR TRIGGERS (M18)
MAX. RUN TIME (M1812)
Default value:
900
s
Setting range:
4
to
36000
seconds (4 seconds to 10 hours)
71
Actuator controls
Manual
AUMATIC AC 01.1/ACExC 01.1 Foundation Fieldbus
EDIT
M4016
MONITOR TRIGGERS
FUNCTION ACTIVE
:EDIT
↵
:OK
C:ESC
EDIT
M1812
MAX. RUN TIME
900 s
:EDIT
↵
:OK
C:ESC