7.6
Positioner (operation mode SETPOINT MODE)
The positioner records position setpoint E1 and position feedback E2 for
comparison. Depending on the detected deviation, the actuator motor then
runs in direction OPEN or CLOSE.
Ò
Set selector switch to position REMOTE.
If the positioner is active, the display shows:
Information
If the display shows
REMOTE MODE
, the actuator is set to open-close duty
and no modulation is performed. In this case, modulating duty has to be
selected first, refer to page 53.
Table of contents:
7.6.1 Adaptive behaviour: switch on or off
7.6.2 Overrun (inner dead band): manual setting
7.6.3 Max. error variable (outer dead band): manual setting
7.6.4 Dead time setting
7.6.5 Closing fully/opening fully (end position tolerance for setpoint E1)
7.6.6 Open-close and modulating duty selection
7.6.7 Source of setpoint E1: view
7.6.8 Input range of setpoint E1: view/edit
7.6.1 Adaptive behaviour: switch on or off
As standard, the adaptive positioning is switched on, i.e. overrun and max.
error variable are automatically defined by the positioner (figure 9).
If the setting is to be made manually, the
ADAPTIVE BEHAVIOUR
parame-
ter must be in position
OFF
.
Æ
Via the menu to parameter:
MAIN MENU (M0)
CONFIGURATION (M4)
SPECIAL FUNCTIONS (M40)
ADAPTIVE BEHAVIOUR (M4011)
Default value:
ON
È
Description of the parameter settings:
OFF
Adaptive behaviour switched off.
ON
Adaptive behaviour switched on.
50
Actuator controls
AUMATIC AC 01.1/ACExC 01.1 Foundation Fieldbus
Manual
SETPOINT MODE
S0
E1
60%
E2
60%
SETPOINT POSITION
EDIT
M4011
ADAPTIVE BEHAVIOUR
ON
:EDIT
↵
:OK
C:ESC