VIEW ENABLED
The parameters for the stepping mode are indicated in the display.
7.7.2 Stepping mode: switch on or off
Stepping mode can be individually activated for the directions OPEN and
CLOSE.
Æ
Via the menu to parameter:
MAIN MENU (M0)
SETTINGS (M1)
STEPPING MODE (M17)
DIRECTION OPEN (M170)
DIRECTION CLOSE (M1715)
Default values:
DIRECTION OPEN = OFF
DIRECTION CLOSE = OFF
È
Description of the parameter settings:
OFF
Stepping mode is switched off
REMOTE ONLY
Stepping mode only possible in operation mode REMOTE.
LOCAL ONLY
Stepping mode only possible in operation mode LOCAL.
REMOTE AND LOCAL
Stepping mode in operation modes REMOTE and LOCAL possible
7.7.3 Stepping range setting (start and end of stepping mode).
For both directions the stepping range (start and end of stepping mode) can
be set separately.
Æ
Via the menu to parameter:
MAIN MENU (M0)
SETTINGS (M1)
STEPPING MODE (M17)
START STEP OPEN (M1713)
STOP STEP OPEN (M1714)
START STEP CLOSE (M1718)
STOP STEP CLOSE (M1719)
Default values:
START STOP
OPEN
=
0.0 %
STOP STEP
OPEN
=
100.0 %
START STEP
CLOSE
=
100,0 %
STOP STEP
CLOSE
=
0.0 %
Setting ranges:
START STEP
OPEN
=
0.0 %
to
99.9 %
STOP STEP
OPEN
=
0.1 %
to
100.0 %
START STEP
CLOSE
=
0.1 %
to
100.0 %
STOP STEP
CLOSE
=
0.0 %
to
99.9 %
57
Actuator controls
Manual
AUMATIC AC 01.1/ACExC 01.1 Foundation Fieldbus
EDIT
M1710
DIRECTION
OPEN
OFF
:EDIT
↵
:OK
C:ESC
EDIT
M1714
STOP STEP
OPEN
100.0 %
:EDIT
↵
:OK
C:ESC
EDIT
M1713
START STEP OPEN
0.0 %
:EDIT
↵
:OK
C:ESC