7.4.2 Intermediate positions: switch on or off
Each intermediate position (
POS.1
to
POS8.
) may individually be switched
on/off.
Æ
Via the menu to parameter:
MAIN MENU (M0)
SETTINGS (M1)
INTERMED. POSITION (M1C)
POS.1 SELECTOR SW. (M1C12)
Default value:
OFF
È
Description of the parameter settings:
OFF
Intermediate position switched off.
REMOTE ONLY
Intermediate position only active in operation mode REMOTE.
LOCAL ONLY
Intermediate position only active in operation mode LOCAL.
REMOTE AND LOCAL
Intermediate position active in operation modes REMOTE and LOCAL.
7.4.3 Intermediate position definition
Each intermediate position (
POS.1
to
POS.8
) can be set to any value
between 0 % and 100 % of the travel.
This function is only available the with position feedback.
Æ
Via the menu to parameter:
MAIN MENU (M0)
SETTINGS (M1)
INTERMED. POSITION (M1C)
POS.1 (M1C10)
Default value:
0,0 %
Setting range:
0.0 %
to
100.0 %
of the travel
(from OPEN to CLOSED)
44
Actuator controls
AUMATIC AC 01.1/ACExC 01.1 Foundation Fieldbus
Manual
EDIT
M1C12
POS.1 SELECTOR SW
OFF
:EDIT
↵
:OK
C:ESC
EDIT
M1C10
POS.1
0.0 %
:EDIT
↵
:OK
C:ESC