7.6.7 Source of setpoint E1: view
This value is set in the factory and can only be changed by the AUMA ser-
vice.
Æ
Via the menu to parameter:
MAIN MENU (M0)
CONFIGURATION (M4)
SETUP (M41)
SETPOINT E1 (M4100)
Default value:
FOUNDATION FIELDBUS
È
Description of the parameter settings:
NONE
There is no setpoint source available.
LOGIC ANALOG IN1
For AUMA service only (the setpoint E1 is transmitted from external via the
analogue input 1 directly to the logic board).
I/O1 ANALOG IN1
The setpoint E1 is transmitted via the I/O board interface, analogue input 1.
I/O1 ANALOG IN2
The setpoint E1 is transmitted via the I/O board interface, analogue input 2.
FOUNDATION FIELDBUS
The setpoint E1 is transmitted via the Foundation Fieldbus interface board.
FF ANALOG IN1
The setpoint E1 is transmitted via the Foundation Fieldbus interface board,
analogue input 1.
FF ANALOG IN2
The setpoint E1 is transmitted via the Foundation Fieldbus interface board,
analogue input 2.
54
Actuator controls
AUMATIC AC 01.1/ACExC 01.1 Foundation Fieldbus
Manual
VIEW
SETPOINT E1
FOUNDATION FIELDBUS
C:ESC