FAIL OPEN
The actuator runs to end position OPEN
FAIL TO PRESET
The actuator runs to a predetermined position.
Preset position definition
If the
FAIL TO PRESET
failure action (
FAILURE POSITION
parameter)
is set, the actuator runs to the preset position stated here.
Æ
Via the menu to parameter:
MAIN MENU (M0)
SETTINGS (M1)
FAILURE BEHAVIOUR (M15)
PRESET POSITION (M1513)
Standard value:
0.0 %
Setting range:
from
0.0 %
to
100.0 %
(from OPEN to CLOSED)
Failure delay time setting
Determines the time elapsed between the recognition of a cable break and
the initiation of the failure action.
Æ
Via the menu to parameter:
MAIN MENU (M0)
SETTINGS (M1)
FAILURE BEHAVIOUR (M15)
DELAY TIME (M1511)
Default value:
3.0
s
Setting range:
0.0
to
1200.0
seconds (20 minutes)
39
Actuator controls
Manual
AUMATIC AC 01.1/ACExC 01.1 Foundation Fieldbus
EDIT
M1513
PRESET POSITION
0.0 %
:EDIT
↵
:OK
C:ESC
EDIT
M1511
DELAY TIME
3.0 s
:EDIT
↵
:OK
C:ESC