5.3.2 Source of the torque signal E6: view
This value is set in the factory and can only be changed by the AUMA ser-
vice.
Æ
Via the menu to parameter:
MAIN MENU (M0)
CONFIGURATION (M4)
SETUP (M41)
TORQUE E6 (M4103)
Default value:
depending on actuator
È
Description of the parameter settings:
NONE
There is no electronic torque monitoring available.
LOGIC ANALOG IN1
The torque signal is transmitted from an external sensor via the logic board
to the analogue input 1.
MWG
The torque signal is generated using the MWG installed in the actuator.
5.3.3 Feedback signals (configuration) via analogue output 1: view
Configuration of analogue output 1 (of the I/O).
Designation in the wiring diagram: ANOUT1.
This value is set in the factory and can only be changed by the AUMA ser-
vice.
Æ
Via the menu to parameter:
MAIN MENU (M0)
CONFIGURATION (M4)
SETUP (M41)
I/O1 ANALOG OUT1 (M410A)
Default value:
POSITION E2
È
Description of the parameter settings:
NOT USED
Analogue output 1 not used.
FEEDBACK E2:
Position feedback (analogue output 1 assigned to actual position signal).
If the actuator is equipped with a position transmitter (potentiometer, RWG
or MWG), an analogue position feedback (galvanically isolated) is available
as a 0/4 – 20 mA signal at the electrical connection (see wiring diagram). An
adjustment to the end positions or the defined travel is not required. An
automatic adjustment is done via the end positions (LSC (WSR) and LSO
(WOEL)).
28
Actuator controls
AUMATIC AC 01.1/ACExC 01.1 Foundation Fieldbus
Manual
VIEW
I/O1 ANALOG OUT1
POSITION E2
C:ESC
VIEW
TORQUE E6
MWG
C:ESC